250kw Biogas Genset in Sound Proof Canopy for Waster Water Plant

Product Details
Customization: Available
After-sales Service: Local Network
Warranty: One Year
Manufacturer/Factory
Diamond Member Since 2021

Suppliers with verified business licenses

Audited Supplier

Audited by an independent third-party inspection agency

Registered Capital
10000000 RMB
Plant Area
501~1000 square meters
  • 250kw Biogas Genset in Sound Proof Canopy for Waster Water Plant
  • 250kw Biogas Genset in Sound Proof Canopy for Waster Water Plant
  • 250kw Biogas Genset in Sound Proof Canopy for Waster Water Plant
  • 250kw Biogas Genset in Sound Proof Canopy for Waster Water Plant
  • 250kw Biogas Genset in Sound Proof Canopy for Waster Water Plant
  • 250kw Biogas Genset in Sound Proof Canopy for Waster Water Plant
Find Similar Products

Basic Info.

Model NO.
CM250S13B
Gas Source
Biogas
Certification
CE, Atex
Power
220kw
Standard
Standard
Biogas Engine Model
Sinotruk Mt13
Alternator Model
Henjo
Rated Volt
400V/230V
Rated Frequency
50/60Hz
Power Factor
0.8
Rated Speed
1500rpm/1800rpm
No. of Cylinders
6
Cylinder Bore
126mm
Piston Stroke
166mm
Displacement
12.419L
Exhaust Temp Before Turbo
Less Than 650ºC
Lubricating Type
Press and Spray Lubrication
Cooling Type
Water Cooling
Start Type
Motor Start
Compression Ratio
11.5:1
Transport Package
Wooden Box
Trademark
CUSUNMACH
Origin
China
HS Code
85022000
Production Capacity
3000 Sets Per Year

Product Description

1. Main structure of the biogas generator set

Biogas generator sets include biogas-fueled reciprocating internal combustion engines, alternators, electrical parts, control devices, cooling systems, lubrication systems, exhaust systems, fuel systems, and auxiliary equipment. Except for the exhaust pipe and silencer of the exhaust system, they are mounted on a steel chassis. The generator set is a fixed permanent installed generator set. The steel underframe is mounted to the concrete foundation.


2. Main structure of the biogas engine

The engine's technology is from the German MAN and represents the most advanced engine in the world. It has undergone rigorous bench test, and its life is longer than other domestic engines. Its functional components and functional design make its components. The number is reduced by about 25% compared to conventional engines, and the maximum program reduces sealing components, greatly reducing the risk of "three leaks". The cylinder parts of the engine are made of vermicular graphite cast iron, which has high tensile strength and fatigue strength. Compared with the gray cast iron collective, the strength is increased by 75%.

3. Technical characteristics of gas engine

Inheriting advanced technology and excellent quality of German MAN's engine. And with below characteristics (1) Iridium spark plugs significantly the service life of spark plugs, (2) EControls new generation of CFV gas supply system ensures the high reliability, (3) Electronically controlled pressure regulating air inlet guarantees low gas consumption and low exhaust temperature, (4) Wide domain oxygen sensor controls fuel-air ratio which ensures economic and environmental emission standard, (5) All condition closed-loop control to achieve the optimal combustion

250kw Biogas Genset in Sound Proof Canopy for Waster Water Plant


4. Alternator

The brushless constant-voltage synchronous alternators are of the self-excited type with an electronic voltage regulator integrated in the excitation system. They are used as main or standby units in land based power installations and for ships' electrical systems and can be driven by internal combustion engines or gas, steam and water turbines and electric motors.

Structure: 
The alternator comprises the main machine exciter and excitation system. The main machine is of revolving magnetic field with cylindrical rotor and damper winding. The exciter is revolving armature machine. The exciter power is supplied to the rotor of the main machine via rotating rectifiers.

250kw Biogas Genset in Sound Proof Canopy for Waster Water Plant

5. Genset control panel


The control panel adopted Harsen controller and can detect the current, voltage, speed, frequency, power, engine cooling water temperature, engine oil pressure, exhaust temperature, number of starts, running time, etc. of the unit. The screen also designed a variety of necessary protections for the generator set to ensure safe and stable operation of the unit. The main protections include high water temperature, low oil pressure, overspeed, high temperature, over voltage, under voltage and low frequency. The control panel provides DC power switch, emergency stop button, and unit fault alarm indication.

The automatic generator set adopts automatic control system, which can realize self-starting, self-regulating, self-adjusting frequency, automatic load-carrying, automatic fault alarm, automatic control, etc., to achieve digital management, the generator is always ready to start, the main power supply is cut off or When the fault occurs, the standby unit starts immediately and is put into the load operation at 15S. The unit is interlocked with the external power. The automatic switching between the mains and the standby unit is realized through the ATS of the Party A. When the utility power is restored, the standby unit exits and enters the shutdown process. When the startup is unsuccessful for 3 consecutive times, it can issue a startup failure alarm, and automatically stop when the unit fails, and provide alarm signal information.

250kw Biogas Genset in Sound Proof Canopy for Waster Water Plant

6. Parameter table
 
CM220S13B biogas generator set
Genset model CM220S13B
Engine model Sinotruk MT13
Alternator model Henjo or equivalent
Controller Harsen
Max power 250kw
Continuous output 220kw
Rated voltage 400V
Power factor 0.8 (lagging)
Rated frequency 50Hz
Rated speed 1500rpm
Steady state voltage regulation rate ≤±2.5%
Stabilization time ≤1.5s
Transient state voltage regulation rate ≤ ±20%
Fluctuation rate ≤±0.5%
Steady state frequency regulation rate ≤0-5% (adjustable)
Stabilization time ≤5s
Transient state frequency regulation rate ≤±10%
Fluctuation rate ≤±0.5%
Starting method 24V DC start
Voltage regulating method AVR (Automatic voltage regulation)
Speed governing method Electronic governor
Ignition system Digital ignition system
Cooling mehtod Forced water cooling with multi-fans radiator
Coupling method Flexible coupling
Reference dimension  3200x1300x1800mm (the drawing will be presented after signing of contract)
Reference weight 3000kg 
Biogas engine data
Model Sinotruk MT13
Engine type Four strokes, spark plug ignited, water cooled, turbocharged and inter-cooled
Cylinder arrangement 6 in line
Bore 126mm
Stroke  166mm
Displacement 12.419L
Rated speed 1500rpm
Idle speed 800±50
Compression ratio 11.5:1
Fuel gas consumption 210g/kwh
Noise level 97db@1meter
Exhaust gas temperature (after turbo) 560ºC
Exhaust gas back pressure 10-12kpa
Oil capacity 40L
Oil consumption 1.5g/kwh
Steady speed regulation 0-5% adjustable 
Cooling method Forced water cooling, multi-fans radiator
Lubricating method Pressure and splashing lubricating
Ignition method Spark plug ignition
Starting method 24V DC start
Rotating direction Counterclockwise (flywheel view)
Output method Flywheel output
Alternator data
Model Henjo 
Rated capacity 312.5kva
Rated voltage 400V
Rated frequency 50Hz
Power factor 0.8 (lagging)
Rated speed 1500rpm
Protection class IP23
Insulation class H
Phases and connection 3 phases and 4 wires
Exciting method Brushless
Voltage regulating method AVR automation

250kw Biogas Genset in Sound Proof Canopy for Waster Water Plant250kw Biogas Genset in Sound Proof Canopy for Waster Water Plant250kw Biogas Genset in Sound Proof Canopy for Waster Water Plant250kw Biogas Genset in Sound Proof Canopy for Waster Water Plant

Send your message to this supplier

*From:
*To:
*Message:

Enter between 20 to 4,000 characters.

This is not what you are looking for? Post a Sourcing Request Now
Contact Supplier